Climate values come from the nearest weather station of NOAA’s GHCN-Daily network (for the UK, Met Office stations): at most 40 km away, at most 150 m higher or lower, daily highs and lows from 1991 to 2025. Daily mean = (max + min) ÷ 2. Flagged values are discarded.

Design temperature (estimate): EN 12831 uses the lowest two-day mean temperature reached or undercut ten times in twenty years. We take each winter 1991/92–2019/20’s lowest two-day mean and use the median (a winter counts with at least 90 % valid days from November to March). This is an estimate from measurements, not a value from a national standard table (such as CIBSE Guide A).

Degree days (base 20/15): sum of (20 °C − daily mean) over the days with a daily mean below 15 °C; mean of the complete years 2016–2025, with 1991–2020 for comparison. UK degree-day tables often use a 15.5 °C base; the 20/15 convention is used here because the heat-loss formula below needs the indoor temperature.

From fuel use: heat demand = fuel use × boiler efficiency; heat loss = heat demand × (20 °C − design temperature) ÷ (24 h × degree days); heat pump electricity = heat demand ÷ SCOP, spread over the months by their degree days. This does not replace a room-by-room heat loss survey by an installer.

Station data are downloaded and checked again every month.

Sources

Menne, M.J., et al. (2012): Global Historical Climatology Network - Daily (GHCN-Daily), Version 3. NOAA National Climatic Data Center. doi:10.7289/V5D21VHZ.